Three different versions can be built: Standard, Enhanced and Special Version. Main technical specifications are presented in Table 1.

The Standard version is based on the currently commissioned and tested first prototype MARTA-01. The prototype allows to reach the cooling power maximum 170W at -30°C (tambient 22°C) and 300 W at -25°C, (tambient 22°C), although some system components are currently being optimized and in next units it is expected to reach up to 200 W at -30°C, tambient 22°C).

The Enhanced version allows to reach the cooling power up to 300W at -30°C (tambient 22°C).

Both versions are currently being optimized and in the new MARTA units the cooling power is expected to be at the level of specified in Table 1.

The Special Version specification shows the maximum reachable cooling power with currently developed set up. It can be offered as an individually designed, custom made unit.

marta1

 

Table 1. Technical specification of three different versions: Standard, Enhanced and Special Version.

 

Standard

Enhanced

Special Version

 

Cooling power

max. 200 W
at -30°C,

tambient 22°C
(300W at -25°C)

max. 300 W
at -30°C,

tambient 22°C

max. 600 W
at -30°C,

tambient 22°C

CO2 mass flow rate

controlled 0-4 g/s

controlled 0-4 g/s

controlled 0-4 g/s

Max. head pressure

6 bar

6 bar

6 bar or TBD

Mass flow-meter

optional

optional

optional

Size [HxWxD] mm

1370x780x700

1370x780x700

TBD

Total weight [kg] ~180 ~210 TBD

Power Supply Standard

230 V/AC, 50 Hz

230 V/AC, 50 Hz

TBD

Max. electric power [kW] 1,5 3,1 TBD
Average electric power consumption @ -30ºC Set point TBD TBD TBD

Other Power Supply standards

optional

optional

optional

Control system

PLC+HMI

PLC+HMI

PLC+HMI

Connectivity and Remote Access

optional

optional

optional

Desktop software

optional

optional

optional

Data Logging

standard

standard

standard

Analog Input and Output

optional

optional

optional

Digital input and Output

optional

optional

optional

CO2 Transfer Line (standard 3m)

optional

optional

optional

Local Box

optional

optional

optional

Special functions

TBD

TBD

TBD

 